The H1 inverters were developed with industry requirements in mind. The H1 is a series of compact, high-efficiency inverters for a wide variety of applications. Thanks to removable control terminals, ability ot use an external panel and side-by-side installation, the H1 series is easy to install and maintain. The inverter can realize U/f or SVC control and have a built-in PID regulator.
Features- operation modes:
- U/f
- SVC
- compatible with asynchronous, synchronous and single-phase motors
- maximum frequency of 1000 Hz
- improved heat dissipation allowing side-by-side installation
- low-power units can be mounted on a TS35 rail
- short-circuit protection, phase loss protection, overload protection
- STO safety input
- compatible with Modbus RTU
- built-in PID regulator
- automatic voltage and current limiting
Input/Output
- 10 binary inputs – NPN or PNP
- 2 analog inputs – current or voltage
- 3 relay outputs
- 2 analog outputs – current or voltage
- 1 three-wire STO safety input
Technical parameters
Technical parameters | Description | |
---|---|---|
Power input | Input voltage range | three-phase 380-440V, 50/60Hz single-phase 200-240V, 50/60Hz |
Output | Output voltage range | 0V to rated voltage input |
Frequency range | 0-1000Hz | |
Overload capacity | 150% rated current for 60s, 180% rated current for 2s |
|
Control parameters | Control modes | U/f, SVC |
Compatible motors | asynchronous, synchronous, single-phase |
|
Starting torque | 0,5Hz/150% rated torque | |
Speed range | 1:100 | |
Frequency precision and resolution | ±0,01% max frequency for digital setting, ±1% max frequency for analog setting |
|
Acceleration/decelleration curve | line, S-curve |
|
Current limiting | automatic during operation | |
Operation parameters | Start signal source | keypad, terminals, serial communication |
Speed signal source | digital setting, analog setting, multistep operation, serial communication |
|
Protection | overcurrent, overvoltage, low voltage, overheat, overload, phase loss, short to ground, output short-circuit |
|
Serial communication | Modbus RTU | |
Operator panel | Displayed values | output frequency, output current, output voltage, bus voltage, two custom parameters, current error |
External keyboard | supported | |
Environmental parameters | Location | indoors, protected from direct sunlight, free from dust, combustible or corrosive vapors and gasses |
Altitude | loss of operation quality above 1000m altitude, circa 10% per 1000m | |
Ambient temperature | -10°C to +40°C, loss of operation quality above +40°C | |
Relative humidity | between 5% and 90% (non-condensing) | |
Storage temperature | -40°C to +70°C | |
Vibration resistance | under 5,9m/s (0,6g) |